8-Channel Programmable Controller for Oxygen, Carbon Dioxide & Combustible Gas Detectors

Item : 99196-Discontinued | Discontinued

Product Summary

The PureAire 8-Channel Controller is designed to provide simple analog control or full-featured digital control of toxic, LEL, and oxygen deficiency monitors. The controller remotely powers and operates up to 8 monitors up to 100 feet from the controller. Capable of accepting any two or three-wire gas detector, it features two user-adjustable common alarm relays which will, in the event of a gas leak, or a fault from one of the monitors, alert personnel.

The multi-channel controller incorporates various modes of operation for taking channels offline individually for performing calibration or sensor maintenance. Each channel can be individually designated with PPM, PPB, or %. The LCD screen displays the readings from all 8 channels simultaneously, and the trends from each channel may be viewed in graph form over a period of time.

This product has been discontinued and replaced with item# 99233-8-Channel Touch Screen Programmable Controller. Please contact PureAire at info@pureaire.net / (888)788-8050 for more information. 

  • Designed to control and power 8 monitors
  • Connects any 2-wire or 3-wire gas sensors
  • Digital and graphic LCD gas concentration display
  • RS-485/Modbus RTU output
  • Built-in power supply
  • NEMA 4X IP67 Water-Resistant Enclosure
  • Two-year warranty

The PureAire Multi-channel Controller connects 2-wire or 3-wire to oxygen monitors, analyzers, or gas detectors. The built-in power supply allows the multi-channel controller to power the monitors located up to 100 feet away. The 2 adjustable relays allow you to create desired audible warnings notifying workers.

PureAire’s Controller comes pre-wired for easy installation. Simply connect the gas monitors to the Controller, and connect the built-in power supply to the main power source.

The 8-channel controller allows users to take channels offline individually for easy calibration or sensor maintenance. While one channel is offline, the other systems will continue to operate normally.

The multi-channel controller allows you to set specifications for each gas sensor for quick differentiation. The LCD graphical display shows current data across all connected channels or trend data over a selected time period. You can manage controller display data in percentage, parts-per-million (PPM), or parts-per-billion (PPB). An RS-485 Modbus communication interface is available upon request.

Specifications

Multi-Controller 8 toxic gas and oxygen monitors. 2-wire loop or 3-wire input
Display LCD graphic display
Humidity 0 – 90% non-condensing
Signal Outputs 2 Relays, NO type (1A, 24VAC / 35 VDC)
Operating Temperature -32 to +122F
Display 3/4″ LCD Digital Display, BackLit
Communication Interface Modbus RTU (RS485)
Power Requirements 115 / 230VAC 50/60HZ
Dimensions 10.03 in x 8.68 in x 6.16 in (254.76mm x 220.47 mm x 157.2 mm)
Weight 6.2 lbs 2.8 kg
Country of Origin USA
Harmonized Tariff Code 8537.10.90.60
Additional Accessories List Price
Horn and Strobe  US (P/N # 42002)
Remote Display US (P/N # 99091)

99196 8-Channel Controller Product Literature

99196 8-Channel Controller Manual

99196 Reset Factory Defaults

99016 – Oxygen Deficiency Monitor
99016 PureAire Oxygen Deficiency Monitor

ST-48 Combustible Gas Monitor

99030 – Universal Gas Detector

Flameproof / Hazardous Location Strobe with optional Horn

Scalable Monitoring

Support multiple monitor inputs so you can expand coverage as your facility grows.

Centralized Alarms

Manage alarm status and notifications from one location for faster response.

Simplified Operations

Streamlines monitoring across rooms, zones, or production areas with unified control.

Integration Friendly

Designed to fit common safety and automation workflows (facility alarms and reporting).

Oxygen deprivation is a silent killer. Oxygen-depleting gases, such as nitrogen, argon, and helium, are odorless and colorless, making leaks impossible to detect, unless appropriate monitoring is in place.

PureAire oxygen deficiency monitors can be used to monitor nitrogen, argon, and helium. Carbon dioxide can also be monitored with PureAire’s dual oxygen/carbon dioxide monitor.

PureAire uses a proprietary, non-depleting, zirconium oxide sensor that will last up to 10 years in a normal environment without needing to be replaced.

PureAire’s sensors do not operate under partial pressure, meaning that a PureAire sensor will not need to be adjusted to account for different elevations. Additionally, the sensors will not drift due to changes in barometric pressure.

In contrast, other gas detection companies use depleting, electrochemical sensors. These sensors, because they are depleting, operate for 1-2 years before needing to be replaced. Electrochemical sensors do not offer long-term solutions to companies committed to safety.

PureAire sensors are built to last 10 years. Often, the sensors work much longer. In fact, some of our first customers who started using PureAire products in 1997 report that the sensors are still in operation today.

On the other hand, an oxygen monitor that uses a depleting, electrochemical sensor is like a battery in that, as the sensor depletes, it begins to lose its power and responsiveness. In order to operate accurately, electrochemical sensors must be calibrated frequently.

PureAire sensors are made of non-depleting zirconium oxide, and calibration is typically not required.

However, a visual check of the monitor should be done once a year to verify that the sensor is functioning properly, and span adjustments should be done, as necessary. The sensor requires periodic testing with nitrogen to verify the sensor’s response to low oxygen levels.

In contrast, electrochemical sensors, because they deplete over time, will need to be calibrated every 2-3 months and totally replaced every 1-2 years.

Switching to a PureAire non-depleting, zirconium oxide sensor will save you time and money, while ensuring the safety of your workers and facility.

Electrochemical sensors offered by other gas detection companies lose accuracy over time and must be calibrated. Calibration recharges and resets the monitor to get an accurate reading. It is important to note that an electrochemical sensor can only be calibrated a finite number of times before it must be discarded.

PureAire’s non-depleting zirconium oxide sensor will not experience drift. Oxygen sensors from PureAire will provide long-lasting, reliable, and accurate monitoring for an average of10+ years.

The oxygen monitor covers an area of approximately 692 square feet when mounted on a wall and should be placed no more than 21 feet from potential leak sources such as gas lines, gas cylinders, or any areas where a gas leak might be expected to occur.

To ensure safety, the maximum distance between two monitors mounted to the same wall, should not exceed 30 feet. However, since cryogenic gases, such as argon, helium, and nitrogen, are unpredictable, we encourage you to contact PureAire for additional guidance specific to your needs.

In most circumstances, PureAire recommends that oxygen monitors be installed 3-5 feet away from gas cylinders or cryogenic gas lines. To enable employees to see the monitor display and verify its performance, PureAire recommends mounting an oxygen monitor 3-5 feet off the ground.

There are other options for mounting an oxygen monitor. For instance, PureAire sensors can sample the air from up to 100 feet away, or be installed within a glovebox, freezer, sealed chamber, or even underground. PureAire monitors can also work in environments that require KF-25 flanges, as well as in nitrogen/argon enriched environments.

PureAire’s Sample Draw Monitors pull a sample flow at a rate of 250 ccs per minute. We recommend using 1/4” OD x 3/16” ID polypropylene sample tubing. Using this internal tubing dimension, to calculate transport (response) time, add 2 seconds per foot of sample tubing. For example, if the sample tube is 10 feet long, the initial response time would be 20 seconds (10ft x 2seconds=20seconds) at 15 feet the response time would be 30 seconds (15ft x 2seconds=30seconds), etc.

The response time when using the entire 100 feet of sample tube will take 3.5 minutes (100ft x 2seconds=200seconds or 3.5minutes) for the sample to reach the monitor.